The expansion boards listed below expand the functionality and I/O count of the RUG9.   The RUG9 has 8 slots per card cage enabling up to 512 I/O points per unit (8 card cages). All boards below can be used in the RUG9's base card cage.


RUG9 expansion card cages are limited to analog and discrete I/O expansion boards and the loop supply board.   For installation, each board slides into the unit's expansion slot and is secured with a cover plate using a single screw.  All discrete wiring connections are made to the boards using a removable Euro-style screw header that can accept up to 12-guage wires.


Click on the expansion board title to view the board's block diagram.


Not exactly sure which board you've got?  Match the part number printed on the board to those listed below.

4 CHANNEL ANALOG INPUT

   -16 bit resolution, 4 channel analog input board.
   -Compatible with 4-20 mA industry standard current loops.
   -Full channel to channel optical isolation enables insertion into existing current loops.
   -Factory calibration stored in onboard EEPROM.
   -Onboard protection against reverse voltage application and overvoltage.

   Order code: R9AI4/16          Part #: 003050


8 CHANNEL ANALOG INPUT

   -2500 V opto-isolation per channel.
   -Inputs can be 4-20 mA or 0-5 VDC.
   -Onboard factory calibration stored in EEPROM.
   -Onboard field power supply allows readings down to zero volts, zero milliamps.

   Order code: R9AI8          Part #: 790140


4 CHANNEL ANALOG OUTPUT

   -2500 V opto-isolation per channel.
   -12-bit resolution, 4-20 mA standard.
   -Onboard factory calibration stored in EEPROM.
   -Complies with 50 VDC loops.
   -Reverse voltage protected.

   Order code: R9AO4          Part #: 992180


COMBO

   -Replaces up to 4 other boards.
   -2-AI's, 4-DI's, 2-relay outputs, 24 VDC loop supply.
   -All I/O optically isolated.
   -AI's 12-bit resolution, 4-20 mA or 0-5 VDC compatible.
   -DI's 24 VDC or 120 VAC compatible.
   -Relays 3 amp/120 VAC.
   -Loop supply 24 VDC/160 mA regulated and isolated.

   Order code: R9COMBO          Part #: 890250


CPU

   -32-bit microprocessor.
   -256KB battery backed low power static RAM.
   -512KB FLASH.

   Order code: R9CPU          Part #: R9 CPU


DIALER

   -Flash memory storage of up to 12 minutes of speech.
   -Uncompressed speech is clear and language independent.
   -Easy recording using built-in microphone.
   -Phone interface supports autodialing/autoanswer.
   -Software provides for easy verbal report definition.
   -User can change setpoints from phone.
   -Radio keyer enables speech over radio system.

   Order code: R9DIAL          Part #: 895170


DUAL RS232/RS485

   -Provides 2 RS232 ports OR 2 RS485 ports.
   -Both ports are indivudally jumper selectable as RS232 or RS485.
   -Standard baud rates supported up to 38,400.
   -Standard DB9 female connector.
   -Individual LED indication for RX, TX, RTS, and CTS.

   Order code: R9DUAL-SERIAL          Part #: R9 DUAL SERIAL


8 CHANNEL DIGITAL INPUT

   -2500 V opto-isolation from bus.
   -Inputs can be 12-120 VAC or 12-60 VDC.
   -Only 3 mA required per channel.
   -Can be used as status, pulse duration, or pulse counter inputs.

   Order code: R9DI8          Part #: 795210


8 CHANNEL HIGH-SPEED DIGITAL INPUT

   -Pulse frequency up to 5 KHz.
   -Pulse width down to 50 µs.
   -Inputs 5-24 VDC.
   -2500 V opto-isolation from bus.
   -Only 3 mA required per channel.
   -Used for fast pulse counting.

   Order code: R9DI8-FAST          Part #: n/a


8 CHANNEL DIGITAL INPUT ISOLATED

   -Full channel to channel 2500 V isolation.
   -Inputs can be 12-120 VAC or 12-60 VDC.
   -Only 3 mA requried per channel.
   -Can be used as status, pulse duration, or pulse counter inputs.

   Order code: R9DI8ISO          Part #: 992190


8 CHANNEL DIGITAL OUTPUT

   -4000 V contact to coil isolation.
   -Inputs can be 240 VAC or 30 VDC.
   -3 amps per channel.
   -Can be used as status, control, alarm, or pulse duration outputs

   Order code: R9D08          Part #: 794210


8 CHANNEL SOLID-STATE DIGITAL OUTPUT

   -Inputs can be up to 48 VDC.
   -0.5 amps per channel.
   -Can be used as status, control, alarm, or pulse duration outputs

   Order code: R9D08-SR          Part #: n/a


8 CHANNEL DIGITAL OUTPUT ISOLATED

   -Full channel to channel isolation.
   -4000 V contact to coil isolation.
   -Inputs can be 240 VAC or 30 VDC.
   -10 amps per channel (10A @ 277VAC/30VDC; 12A @ 125VAC).
   -Can be used as status, control, alarm, or pulse duration outputs

   Order code: R9D08ISO          Part #: 990380


FLASH DISK

   -Nonvolatile flash storage requires no batteries.
   -Small size (1.6 x 1.4 in.), rugged cards can be easily transported.
   -Card capacity of up to 2 GB.
   -Cards can be read by standard PC with standard PCMCIA carrier.
   -Time tagged floating point data and event logs are stored as ASCII files.

   Order code: R9FLASH          Part #: 999110


LOOP/CHARGER/DIAGNOSTIC

   -Loop supply 24 VDC/160 mA regulated and isolated.
   -Lead acid battery charger, 160 mA.
   -Onboard diagnostics for AC power fail, battery voltage/fail, temperature.
   -Fuses and diodes protect against reverse voltage application.
   -LED's show bus, loop, and charge status.

   Order code: R9LOOP          Part #: 799040


MODEM/RS232

   -Bell standard tone use, Bell 103/212, 300/1200 baud.
   -Transformer isolation on RCV and TX.
   -Isolated radio key line.
   -Optically isolated ring detector.
   -Adjustable transmit amplitude.
   -Standard RS232 port.
   -Compatible with standard radios, radio modem units, and spread spectrum radios.

   Order code: R9MDM          Part #: 896080


SLEEP CONTROLLER

   -Inputs can be dry contacts, logic or analog.
   -Sleep timer up to 32 hours.
   -Sleep current 1 to 4 mA.
   -Can be awakened by button, contact, touchtone code, phone ringing, high wind speed,
     or analog value out of range.
   -Inputs can count tips and read encoder.

   Order code: R9SLEEP          Part #: 790321